info@tempcontrol.nl | +31 (0) 15 251 18 31

TLI40 - Ascon Tecnologic

TLI40 Digital indicator - Ascon Tecnologic

Digital indicator - Ascon Tecnologic
 

  • Panel mount indicator: 48 x 48 mm, depth 98 mm (1/16 DIN )
  • 1 temperature probe input
  • Up to 4 outputs
  • RS 485 serial interface
  • 1 display 4 digits, h 12 mm, red colour, 3 LED Bargraph

Main features

1 temperature probe input:
- Thermocouples: J, K, S, B, C, E, L, N, R, T
- PTC KTY81-121 (990 Ω @ 25 °C)
- NTC 103AT-2 (10KΩ @ 25 °C)
- RTD : PT100 IEC
- Voltage (V):  0/1...5 V, 0/2...10V
- Voltage (mV): 0...50 mV, 0/12...60mV
- Current (mA): 0/4...20 mA
- Potentiometer: with value higher than 1 KΩ
- IR probes (J.K type)
- Overall accuracy: ± 0,15 % fs
- Sampling time: from 8 to 64 samples/ second for V,C or potentiometer signals
1 digital input - Free Voltage

Keyboard: mechanical - 4 multifunction keys

Up to 4 outputs according to the configuration:
OUT1:
- Relay SPST-NO 5 A-AC1 (2 AAC3/ 250 VAC)
- SSR servomotor drive  (14 VDC/7 mA)
- Analogue output: 0/4 ..20 mA or 0/2 ..10 V
OUT2 to OUT 4
- Relay SPST-NO 5 A-AC1 (2 AAC3/ 250 VAC)
- SSR servomotor drive  (14 VDC/7 mA)

Power supply:
24 VAC/VDC or 100...240 VAC

Auxiliary power supply for external transmitters (optional):
- 12 VDC/20 mA max
- 2,5 VDC/2,5 mA max. for Potentiometers

Functions:
- Acquisition and retransmission
- Indication

Up to 4 configurable alarms with the following  type:
- Probe errors
- Temperature tresholds: (absolute or relative)

Communication and programming:
Communication on TTL port to: 
- Universal programming key
- Remote display
- RS 485 serial interface
- RS 485 port(optional) with ModBus RTU and J-bus (slave) protocols

Programming/configuration tools:
- Easy to use front interface for configuration
- Configuration software available for PC

Mounting method:
panel mount

Case dimensions:
48 x 48 mm, depth 98 mm (1/16 DIN )

Signals connection:
- 2.5 mm² screw terminals block
- 2.5 mm² extractable screw terminals block (optional )
- IP65 front frame protection, with gasket

Display and indicators:
1 display 4 digits, h 12 mm, red colour, 3 LED Bargraph

Connectable to:
- Programming key A01 for PC connection, backup and other functions
- Any controller from Ascon Tecnologic range with the appropriate I/Os
- SCADA for monitoring, traceability and remote management
- DX and DY gateways for remote monitoring

Ascon Tecnologic

Downloads

More information